Product Category

Hydrants

Hydrant category covering Underground Fire Hydrant Valve PN10-16 for fire extinguishing operations and municipal water lines.

Hydrants are used in fire extinguishing and municipal water line applications where a valve connection is required as part of the water supply system.

This category currently includes Underground Fire Hydrant Valve PN10-16, which is used for fire extinguishing operations and municipal water lines.

Available Hydrant Product

Underground Fire Hydrant Valve PN10-16

Underground Fire Hydrant Valve PN10-16 is used for fire extinguishing operations and municipal water lines.

According to the catalog, this hydrant valve can be serviced and handled without detaching the valve from the pipeline. The product is listed in PN10 and PN16 pressure classes.

Applications

  • Fire extinguishing operations
  • Municipal water lines

Design Features

  • Easy and fast service and handling
  • Service without detaching the valve from the pipeline
  • Designed by AICC

Materials

For Underground Fire Hydrant Valve PN10-16, the catalog mentions ductile iron EN1563 GJS400 for the body.

The obturator is made of ductile iron vulcanized with EPDM/NBR according to DIN53538-5.

The spindle is made of stainless steel 1.4021 according to DIN17440, with rolled thread and ultra-burnished sealing surface.

The O-ring material is NBR.

Coating

Inside and outside surfaces of ductile iron parts are coated with a minimum 250 micron epoxy electrostatic coating according to DIN30677.

Standards and Testing

The catalog mentions flange drilling and flange dimensions according to EN1092-2.

Hydrostatic testing is according to ISO5208.

For PN10, the seal test pressure is 11 bar and the body test pressure is 15 bar.

For PN16, the seal test pressure is 17.6 bar and the body test pressure is 24 bar.

Available Sizes

The catalog table lists DN80 and DN100 sizes for Underground Fire Hydrant Valve PN10-16.

Related Product

Underground Fire Hydrant Valve PN10-16

Technical Summary

Hydrants in this category are used for fire extinguishing and municipal water line applications. The current product in this category is Underground Fire Hydrant Valve PN10-16, which is listed in PN10 and PN16 pressure classes. The catalog mentions ductile iron EN1563 GJS400 body, GJS400 and EPDM/NBR obturator, stainless steel 1.4021 spindle, NBR O-ring, EN1092-2 flange dimensions, DIN30677 epoxy coating and ISO5208 hydrostatic testing.

Products

Products in Hydrants

FAQ

What are hydrants used for?

Hydrants are used in fire extinguishing and municipal water line applications.

What product is included in this category?

This category currently includes Underground Fire Hydrant Valve PN10-16.

What is Underground Fire Hydrant Valve PN10-16 used for?

It is used for fire extinguishing operations and municipal water lines.

What pressure classes are listed for this hydrant valve?

The catalog lists PN10 and PN16.

What sizes are listed in the catalog table?

The catalog table lists DN80 and DN100.