Strainer Y Type PN10-16-25

Strainer Y Type PN10-16-25 is used to prevent suspended particles from entering water networks in industrial, agricultural, potable water and pump station applications.

Request Technical Information

Technical Overview

Strainer Y Type PN10-16-25 is used in industrial, agricultural and water line systems, potable water systems and pump stations for non-corrosive liquids with a maximum temperature of 80°C.

The valve is used to prevent suspended particles from entering the water network.

Technical Overview

Strainer Y Type PN10-16-25 is a Y-type strainer used in pipeline systems where suspended particles need to be filtered before entering downstream equipment or the water network.

According to the catalog, this product is used in industrial, agricultural, water line, potable water and pump station applications for non-corrosive liquids.

Applications

  • Industrial systems
  • Agricultural systems
  • Water line systems
  • Potable water systems
  • Pump stations
  • Non-corrosive liquid lines up to 80°C

Function

The main function of this valve is to prevent suspended particles from entering the water network.

The Y-type body arrangement includes a filter element that separates particles from the flow path.

Standards and Dimensions

Flange drilling and flange dimensions are according to EN1092-2.

Other flange standards are available upon request.

Face-to-face length is according to EN558-1 Series F1 / DIN3202-1.

Materials

The body is made of ductile iron EN1563 GJS400.

The cap is made of GJS400.

The filter is made of stainless steel AISI304 according to DIN17440.

The O-ring material is NBR.

Coating

Inside and outside surfaces of ductile iron parts are coated with a minimum 250 micron epoxy electrostatic coating according to DIN30677.

Temperature

The catalog states use for non-corrosive liquids with a maximum temperature of 80°C.

The catalog also mentions suitability for liquid temperatures up to 200°C upon request.

Hydrostatic Test

Hydrostatic testing is according to ISO5208.

For PN10, the body test pressure is 15 bar.

For PN16, the body test pressure is 24 bar.

For PN25, the body test pressure is 37.5 bar.

Available Sizes

The catalog table lists Strainer Y Type PN10-16-25 in DN50, DN65, DN80, DN100, DN125, DN150, DN200, DN250 and DN300 sizes.

Technical Summary

Strainer Y Type PN10-16-25 is used to prevent suspended particles from entering the water network. It is used in industrial, agricultural, water line, potable water and pump station applications for non-corrosive liquids up to 80°C. The catalog mentions ductile iron EN1563 GJS400 body, GJS400 cap, stainless steel AISI304 filter, NBR O-ring, EN1092-2 flange dimensions, EN558-1 Series F1 / DIN3202-1 face-to-face length, DIN30677 epoxy coating and ISO5208 hydrostatic testing.

FAQ

What is Strainer Y Type PN10-16-25 used for?
It is used to prevent suspended particles from entering the water network in industrial, agricultural, water line, potable water and pump station applications.

What fluid condition is mentioned for this strainer?
The catalog mentions non-corrosive liquids with a maximum temperature of 80°C.

What materials are mentioned for this product?
The body is ductile iron EN1563 GJS400, the cap is GJS400, the filter is stainless steel AISI304, and the O-ring is NBR.

What standards are mentioned?
The catalog mentions EN1092-2 for flange dimensions, EN558-1 Series F1 / DIN3202-1 for face-to-face length, DIN17440 for the stainless steel filter, DIN30677 for coating and ISO5208 for hydrostatic testing.

What pressure classes are listed?
The product is listed as PN10, PN16 and PN25.